5 SAFETY APPLICATION CONFIGURATION EXAMPLES
5.2 System to Which Multiple Safety CPUs are Connected
229
5
The following shows the constant and safety user devices used in the program.
Way of using the constant
K: indicates decimal number
Ex.
K1 1 of decimal number
Way of using the safety user devices
Way of using word device bit specification
SA\D.n: This indicates the nth bit of the word device SA\D
Ex.
SA\D0.0 = 0 bits in SA\D0
For bit-specified word device, refer to the following.
MELSEC iQ-R Programming Manual (Instructions, Standard Functions/Function Blocks)
Safety user devices Description
SA\D0 This is used as restart status.
(1) SA\D0 = 0: Initial status or start processing completed
(2) SA\D0 = 1: (SA\D0.0: ON): Reset switch pressed
(3) SA\D0 = 2 (SA\D0.1: ON): Restart processing completed (reset switch released after pressed in (2))
SA\D1 This is used as start status.
(1) SA\D1 = 0: Initial status or safety not checked
(2) SA\D1 = 1 (SA\D1.0: ON): Reset switch pressed.
(3) SA\D1 = 2 (SA\D1.1: ON): Restart processing completed (reset switch released after pressed in (2))
SA\T0 This indicates timer device. Times out after a lapse of the time specified at K.
0000000000000001
F0