4 ERROR CODE LIST
4.2 C Intelligent Function Module Dedicated Functions
113
4
-339 FEADH Sampling wait suspension error
Since data sampling in each sequence scan was stopped, the
wait processing was interrupted.
When the processing to wait for sampling is required again,
perform it after starting data sampling in each sequence scan.
-340 FEACH Sampling wait cancellation error
Since the status of the control CPU was placed into the STOP/
PAUSE state, the sampling wait state was canceled.
When the processing to wait for sampling is required again,
perform it after starting data sampling in each sequence scan.
-341 FEABH CPU parameter change error
Acquisition of data failed since data sampling was stopped due
to the change of CPU parameters of the control CPU.
Set data sampling in each sequence scan again.
-342 FEAAH Time synchronization operating status setting error
The value specified to the time synchronization operating status
is out of range.
Check the value specified to the time synchronization operating
status.
-343 FEA9H Sampling setting error
The specified device does not exist.
The specified device cannot be used for data sampling in
each sequence scan.
Review the device.
-344 FEA8H Sampling setting error
The specified device is out of range.
Set the device within the range.
-345 FEA7H Maximum number of points error
The total number of device points of each module using the
sequence scan synchronization sampling function of the control
CPU exceeds the maximum number of points.
(The number of device points is calculated by rounding up in
8192 points.)
Review the number of target device points for the sequence
scan synchronization sampling function.
Review the settings of each module using the sequence scan
synchronization sampling function of the control CPU so that
the total number of device points does not exceed the
maximum number.
-346 FEA6H Sampling setting error
The data sampling in each sequence scan setting failed.
Restore the number of device points for data sampling in each
sequence scan to the one before updating the setting.
Cycle the power of the system where the C intelligent function
module is mounted or reset the CPU module.
Review the number of device points for data sampling in each
sequence scan.
Set data sampling in each sequence scan again.