2 CPU MODULE FB
2.3 M+RCPU_MSynchronization_Delay1RST, M+RCPU_MSynchronization_Delay2RST
9
2
FB details
*1 The RCPU that supports the inter-module synchronization function can be used. ( MELSEC iQ-R CPU Module User's Manual
(Startup))
Error code
There is no error code.
Item Description
Available devices CPU module RCPU
*1
Engineering tool GX Works3
Language Ladder diagram
Number of basic steps 12 steps
The number of steps of the FB embedded in a program depends on the CPU module used, the input/output definitions, and the
options setting of GX Works3. For the options setting of GX Works3, refer to the GX Works3 Operating Manual.
Processing When i_bEN is turned on, the function holds the state in the FB and resets o_bData when the FB is called next or the second
time.
M+RCPU_MSynchronization_Delay1RST resets the device when the FB is called next.
M+RCPU_MSynchronization_Delay2RST resets the device when the FB is called second time.
FB compilation method Macro type
FB operation Always executed
Input condition for FB_EN None
Timing chart of I/O signals M+RCPU_MSynchronization_Delay1RST
FB: FB call timing
* M+RCPU_MSynchronization_Delay2RST resets the device at the second FB call timing after FB is once called.
Restrictions or precautions Holds the output by the number of Delays after the status of the CPU module is changed from STOP to RUN.