414
26 REDUNDANT FUNCTION
26.5 System Consistency Check
Execution timing
The following table lists the execution timing of the system consistency check.
*1 Checking the operating status can be disabled in "Backup Mode Setting" of "Redundant Behavior Setting". ( Page 425 Redundant
System Operation Setting)
The function is not executed in the following cases.
One of the systems has not started up (powered off, reset, or initial processing being performed).
A stop error has occurred in the CPU module.
The redundant system is in separate mode.
The memory copy is being executed.
Item Execution timing
Files When both systems are simultaneously powered on or reset
When the other system is powered on or reset while one system is waiting for the other system to start
When the standby system is powered on or reset while the control system is operating
When the operation mode is changed to the backup mode
When the operating status of the CPU module is switched from STOP to RUN
When the END processing is performed
When the online program change is completed
When the systems are switched
When tracking cables are reconnected
Operating status
*1
When the standby system is powered on or reset while the control system is operating
When the operation mode is changed to the backup mode
When the operating status of the CPU module is switched from STOP to RUN
When the END processing is performed
When tracking cables are reconnected
Modules on the main base unit When both systems are simultaneously powered on or reset
When the other system is powered on or reset while one system is waiting for the other system to start
When the standby system is powered on or reset while the control system is operating
When the operation mode is changed to the backup mode
When tracking cables are reconnected
SD memory card When both systems are simultaneously powered on or reset
When the other system is powered on or reset while one system is waiting for the other system to start
When the standby system is powered on or reset while the control system is operating