554
36 ERROR CODES
36.4 List of Error Codes
1133H Socket
communications
response send
error
The response send failed during
socket communications.
Continue Check the operation of the
external device or switching hub.
Since there may be congestion of
packets on the line, send data
after a certain period of time.
Check if the Ethernet
communication load is high
because of the Ethernet functions
being executed. Use the Ethernet
functions so that the
communication load is reduced.
Check if the connection cable is
disconnected.
Check that there is no connection
failure with the switching hub.
Always
1134H TCP connection
timeout
A TCP ULP timeout error has
occurred in the TCP/IP
communication. (The external device
does not send an ACK response.)
Continue Check the operation of the
external device.
Check and correct the TCP ULP
timeout value.
Since there may be congestion of
packets on the line, send data
after a certain period of time.
Check if the Ethernet
communication load is high
because of the Ethernet functions
being executed. Use the Ethernet
functions so that the
communication load is reduced.
Check if the connection cable is
disconnected.
Always
1152H IP address error The IP address is not set correctly. Continue Correct the IP addresses. Parameter
information
Always
1155H Connection
number
acquisition error
The specified connection was already
closed in TCP/IP communications.
Open processing is not performed.
Continue Perform the open processing for
the specified connection.
Check if the open processing has
been performed in the external
device.
Always
1157H Receive buffer
securement
error
The specified connection was already
closed in UDP/IP communications.
Open processing is not performed.
Continue Perform the open processing for
the specified connection.
Check if the open processing has
been performed in the external
device.
Always
1165H UDP/IP send
failed
Data was not sent correctly with UDP/
IP.
Continue Check the settings for connection
with the external device.
Check the operation of the
external device or switching hub.
Since there may be congestion of
packets on the line, send data
after a certain period of time.
Check if the Ethernet
communication load is high
because of the Ethernet functions
being executed. Use the Ethernet
functions so that the
communication load is reduced.
Check if the connection cable is
disconnected.
Check that there is no connection
failure with the switching hub.
Execute a PING test. If the test
completes with an error, take an
action to correct the error.
Always
Error
code
Error name Error details and cause Stop/
continue
Action Detailed
information
Diagnostic
timing