36 ERROR CODES
36.4 List of Error Codes
4025H File related error The specified file is processing the request from
another engineering tool.
Forcibly execute the request. Or, execute the request again
after the processing being performed ends.
4026H File related error The file password set in advance to the target
drive (memory) must be specified.
Specify the file password set in advance, and then access to
the drive (memory).
4027H File related error The specified range is larger than the file size. Check the specified range and access within that range.
4028H File related error The same file already exists. Forcibly execute the request. Or, change the file name and
execute the request again.
4029H File related error The specified file capacity cannot be obtained. Review the specified file capacity, and execute the request
again.
402AH File related error The specified file is abnormal. Back up data in the CPU module, and then initialize the
memory.
402BH File related error The request cannot be executed in the specified
drive (memory).
Set the operating status of the CPU module to STOP, and
execute the request again.
402CH File related error The request cannot be executed currently. Execute the request again after a while.
402FH File related error Writing of a file did not complete. Back up data internally in the CPU module, and delete the
corresponding file or initialize the drive 4. Then, write the file
to the programmable controller again.
Write the program restoration information. Then, read the
program files from the programmable controller again.
4030H Device specification error The specified device is not supported.
When CPU Module Logging Configuration Tool is
used
The data logging specifying a device that is not
supported was started.
Check the specified device.
4031H Device specification error The specified device number is out of range.
The CPU module does not support the specified
device.
When CPU Module Logging Configuration Tool is
used
The data logging specifying a device number that
does not exist was started.
Check the specified device number.
Check the device assignment of the CPU module.
Check the specified device.
4032H Device specification error The device modification was incorrectly
specified. Or, the unusable device (TS, TC, SS,
SC, CS, or CC) was specified in any of the
following SLMP/MC protocol commands; Read
random, Write random (in units of words), Entry
monitor device, or Execute monitor.
When CPU Module Logging Configuration Tool is
used
The data logging specifying a device modification
that is not supported was started.
Check the device modification method.
Check the specified device.
4033H Device specification error Writing cannot be done because the specified
device is for system use.
Do not write the data in the specified device, and do not turn
on or off.
4034H Device specification error The dedicated instruction cannot be executed
since the completion device for the dedicated
instruction does not turn on.
Since the completion device for the SREAD or SWRITE
instruction does not turn on in the CPU module on the target
station, execute the instruction again after setting the
operating status of the CPU module on the target station to
the RUN status.
4040H Intelligent function module
specification error
The request cannot be executed to the specified
intelligent function module.
Check whether the specified module is the intelligent function
module having the buffer memory.
4041H Intelligent function module
specification error
The access range exceeds the buffer memory
range of the specified intelligent function module.
Check the start address and access number of points and
access using a range that exists in the intelligent function
module.
4042H Intelligent function module
specification error
The specified intelligent function module cannot
be accessed.
Check that the specified intelligent function module is
operating normally.
Check the specified module for a hardware fault.
4043H Intelligent function module
specification error
The intelligent function module does not exist in
the specified position.
When CPU Module Logging Configuration Tool is
used
The data logging specifying a device that does
not exist or cannot be accessed was started.
Check the I/O number of the specified intelligent function
module.
4044H Intelligent function module
specification error
A control bus error occurred during access to the
in
te
lligent function module.
Check the specified intelligent function module and other
modules and base units for a hardware fault.
Error
code
Error name Error details and cause Action