36 ERROR CODES
36.4 List of Error Codes
609
36
40CEH Label communication error • An attempt was made to access a label that
cannot be accessed with a label name.
• Change the data type of the specified label to the one other
than "Function Block" or "Pointer".
• Change the class of the specified label to the one other than
"VAR_GLOBAL_CONSTANT".
• Specify a device that is not being modified. (Bit-specified
word devices and digit-specified bit devices can be
specified.)
• Change the data type of the specified label to the one other
than "Bit and two-dimensional array" or "Bit and three-
dimensional array".
40D0H Label communication error • The target CPU module does not support
"Access from External Device" of "Global Label
Setting".
• Disable "Access from External Device", and then write the
data to the programmable controller again.
40D1H Label communication error • When the byte is specified for the unit for
reading/writing data, an odd-numbered value is
specified for the read/write array data length.
• Specify an even-numbered value for the read/write array
data length.
4100H Any other error • Hardware failure of the CPU module. • Replace the CPU module.
4101H Any other error • Serial communication connection was executed
for a different CPU module series.
• Check the CPU module series.
4103H Any other error • The instruction written by online program change
is incorrect or invalid.
• Execute online program change again. Or, set the operating
status of the CPU module to STOP, and write the program.
4104H Any other error • An instruction(s) that cannot be executed by the
CPU module set to process mode or redundant
mode is included in the instructions targeted for
online program change.
• Delete the instruction(s) that cannot be executed, and
execute the online program change function again. Or, set
the operating status of the CPU module to STOP, and write
the program.
4105H Any other error • Hardware failure of the CPU module internal
memory
• The possible cause is a hardware failure of the CPU module.
Please consult your local Mitsubishi representative.
4108H Any other error • The device monitor/test cannot be performed
normally.
• Execute the function again. Check that the access prohibited
area is not accessed, and execute the function again.
410AH Any other error • The specified command cannot be executed
because the online program change is being
executed.
■When CPU Module Logging Configuration Tool is
used
• The data logging where a step No. is specified as
the collection start condition or trigger condition
was started during the online program change.
• The data logging where a label (global label or
local label) is specified as the collection start
condition, data collection target, or trigger
condition was started during the online program
change.
• The data logging setting file where a label (global
label or local label) is specified as the collection
start condition, data collection target, or trigger
condition was written during the online program
change.
• Execute the request again after the online program change.
410BH Any other error • The monitor condition registration was cleared
after the online program change was executed.
• Execute the registration of monitoring condition again after
the online program change.
410CH Any other error • Writing to the specified data is not supported. • Check that the version of the engineering tool used is
correct.
• Check the setting and correct it.
410EH Any other error • When the execution status of the online program
change is in error, the online program change
command was issued.
• Issue the online program change cancel command, and
execute the function again.
410FH Any other error • During the execution of the online program
change function, the cancel command was
issued by the same request source.
• Issue the command again after the currently-performed
processing ends.
4110H CPU module error • The request cannot be executed because the
CPU module is in a stop error state.
• Reset the CPU module and execute the request again.
4111H CPU module error • The request cannot be executed because the
other CPU modules, except the host CPU
module, have not yet started in a multiple CPU
system.
• Execute the request again after all the other CPU modules
have started.
Error
code
Error name Error details and cause Action