EasyManua.ls Logo

Mitsubishi Electric MELSEC iQ-R Series - Page 716

Mitsubishi Electric MELSEC iQ-R Series
760 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
714
APPX
Appendix 7 Processing Time
Link refresh processing time for the CC-Link module
The link refresh processing time between the CPU module and the CC-Link module on the main base unit or the extension
base unit is calculated by the following formulas. (Remote net Ver.1 mode, Remote net Ver.2 mode)
T, R [ms] = KM1 + KM2 ((RX + RY + SB) 16 + RWr + RWw + SW) + U
U [ms] = KM3 (SBU 16 + SWU)
T: Link refresh time (sending side)
R: Link refresh time (receiving side)
U: Unit label (SB/SW) refresh time
RX: Total number of points of remote input (RX) refreshed by the master station/local station
*1
RY: Total number of points of remote output (RY) refreshed by the master station/local station
*1
RWw: Total number of points of remote register (RWw) refreshed by the master station/local station
*1
RWr: Total number of points of remote register (RWr) refreshed by the master station/local station
*1
SB: Number of points of link special relay (SB)
*2
SW: Number of points of link special register (SW)
*2
SBU: Number of points of link special relay (SB)
*3
SWU: Number of points of link special register (SW)
*3
*1 Total number of points here indicates the one of link devices that have been set in "Refresh Setting" and "Network Configuration
Settings".
*2 Number of points here indicates the one of when module label is not used. Calculation is executed while it is regarded as "0" when
module label is used.
*3 Number of points here indicates the one of when module label is used. Calculation is executed while it is regarded as "0" when module
label is not used.
*4 The base units here indicates the type of base unit where the network module targeted for refresh is mounted.
Condition Constant value
KM1 (10
-3
) 40.00
KM2 (10
-3
) Main base unit
*4
0.01
Extension base unit
*4
0.12
KM3 (10
-3
) Main base unit
*4
0.03
Extension base unit
*4
0.15

Table of Contents

Other manuals for Mitsubishi Electric MELSEC iQ-R Series

Related product manuals