APPX
Appendix 7 Processing Time
719
A
Simple CPU communication function
The processing time of the simple CPU communication function (the increase in END processing time for the CPU module)
can be calculated by the following formula.
Processing time of the simple CPU communication function [s] = KM1 + T
1
+ T
2
+ ... + T
n
T
n
[s] = KM2 + KM3 (number of bit points to be communicated 16 + number of word points to be communicated) +
E
n
E
n
[s] = KM4 + KM5 (number of bit points to be communicated 16 + number of word points to be communicated)
Device/label access service processing time
This section describes the device/label access service processing time when "Processing time = One time" in the device/label
access service processing setting.
*1 When data are written to the program using a pointer (P) during RUN, the processing time is extended depending on the pointer number
used. For example, when the data are written to the program using P8191 during RUN, the processing time is extended up to 3.0ms.
T
n
: Simple CPU communication processing time per setting
E
n
: Additional time when the file register (R, ZR) is used (It is added when the file register (R, ZR) is used.)
n: Number of settings
Condition Constant value
Process mode Redundant mode
KM1 85.00 127.00
KM2 5.50 5.50
KM3 0.024 0.024
KM4 1.60 1.60
KM5 When an extended SRAM cassette is not used 0.10 0.10
When an extended SRAM cassette is used 0.13 0.13
Condition Device/label access
service processing
time
Connected via USB Ladder block change during
RUN (online program change)
100 steps are inserted into the head of program of 40K
steps.
1.0ms maximum
*1
Monitor data registration Data register (D) (Number of device points = 32 points) is
registered to monitor.
0.07ms maximum
When connecting the Ethernet
port (TCP)
Ladder block change during
RUN (online program change)
100 steps are inserted into the head of program of 40K
steps.
1.0ms maximum
*1
Monitor data registration Data register (D) (Number of device points = 32 points) is
registered to monitor.
0.07ms maximum
When connecting the Ethernet
port (UDP)
Ladder block change during
RUN (online program change)
100 steps are inserted into the head of program of 40K
steps.
1.0ms maximum
*1
Monitor data registration Data register (D) (Number of device points = 32 points) is
registered to monitor.
0.07ms maximum