1 FUNCTIONS
1.12 Configuration Function
179
1
At the joining/leaving of BACnet
In the following BACnet standards, COV notifications can be sent when joining and leaving BACnet.
ANSI/ASHRAE 2004
IEIEJ-G-0006:2006 Addendum-a
ANSI/ASHRAE 2010
Set the send target of COV notifications when joining/leaving BACnet to the Restart_Notification_Recipients property of a
Device object.
The following shows how to set the Restart_Notification_Recipients property of a Device object.
Operating procedure
1. Select [BACnetObject] to open the "BACnet Objects" screen.
2. Click the [Browse] button of "Device".
3. Click the [Details] button in the row where "ObjectName" is "RJ71BAC96".
4. Click the [Add] button of "Restart_Notification_Recipients".
5. Set the send target of COVs. A send target can be set by specifying either a DeviceID or a BACnetAddress.
How to specify a DeviceID
Enter the instance number of a send target device in the rightmost textbox.
How to specify a BACnetAddress
Select "BACnetAddress" from the leftmost pull-down list, and specify a BACnetAddress by referring to the following section.
Page 104 How to specify a BACnetAddress