1 FUNCTIONS
1.12 Configuration Function
185
1
■ Example of an Event notification send setting
The following shows the setting example to send an Event notification to another BACnet device (instance number of the
device: 3) when the value of the PresentValue property of an AnalogInput object (instance number: 10) in the BACnet module
exceeded the upper limit value.
1. Select [Maintenance] [Pause/Restart], and click the [Pause] button on the "Pause/Restart" screen.
2. Set a send destination of an Event notification (instance number of the device: 3) to the RecipientList property of a
NotificationClass object. (Page 103 Setting RecipientList property)
3. Select [BACnetObject] to open the "BACnet Objects" screen.
4. Click the [Browse] button of "AnalogInput".