226
1 FUNCTIONS
1.12 Configuration Function
Backup/Restore
Configure the settings for backup or restoration of data, such as objects and properties.
Backup
The data of objects and properties are saved in a backup file (*.dat).
Operating procedure
1. Select [Maintenance] [Backup/Restore], and right-click "Backup Information".
2. Click "Save target as"
*1
in the shortcut menu.
3. Save the CSV file to an arbitrary location.
*1 For Internet Explorer
11.0
The log records sampled with a TrendLog object are not saved in a backup file (*.dat).
Restore
Restore the saved data in a backup file (*.dat) to a BACnet module.
Operating procedure
1. Select [Maintenance] [Backup/Restore].
2. Click the [Browse] button and select a backup file (*.dat) to be restored.
3. Click the [Restore] button.
Precautions
If the IP address of a BACnet module is changed after restoration, the BACnet module may not be logged in after restoration.
Before performing restoration, be sure to check the IP address after the restoration.