254
APPX
Appendix 1 I/O Signals
Stop request from a configuration function
When the [Pause] button clicked in a configuration function, an operation stop processing is performed with the following
procedure.
■ CheckYDevice in the BACnet detail setting is '0'
■ CheckYDevice in the BACnet detail setting is '1'
Operation of a BACnet module X0 X1 X2 Remarks
BACnet communication is in operation. 1 1 1
The [Pause] button is clicked in a configuration function.
BACnet leaving processing is performed.
After leaving BACnet, the value of X2 is changed to '0'. 10
Change the value of X1 to '0' to inform the program to stop
the operation.
100
The BACnet communication is stopped. 0
Operation of a BACnet
module
X0 X1 X2 Operation in a program Y1 Remarks
BACnet communication is in
operation.
111 1
The [Pause] button is clicked in a
configuration function.
Change the value of X1 to '0'
to inform the program to stop
the operation.
10
0 After the value of X1 is changed
from '1' to '0', the value of Y1
should be changed to '0'.
10
When the value of Y1 is
changed to '0', a BACnet
leaving processing is started.
0
After leaving BACnet, the
value of X2 is changed to '0'.
10
The BACnet communication is
stopped.
0