88
1 FUNCTIONS
1.1 BACnet Object Function
+16 to +17 Consumed_WH_In_This_Term1 The amount of electric power consumption every 30 minutes from
the monitoring start time is stored.
R/W

+74 to +75 Consumed_WH_In_This_Term30
+76 Consumed_WH_In_This_Term1 (State) The data state of the amount of electric power consumption every 30
minutes from the monitoring start time is stored.
0: Normal
1: Error
2: Disable
R/W

+105 Consumed_WH_In_This_Term30 (State)
+106 to
+107
Consumed_WH_In_Last_Term1 The amount of electric power consumption every 30 minutes from
the monitoring start time which is acquired from the previous
monitoring is stored.
R/W

+164 to
+165
Consumed_WH_In_Last_Term30
+166 Consumed_WH_In_Last_Term1 (State) The data state of the amount of electric power consumption every 30
minutes from the monitoring start time which is acquired from the
previous monitoring is stored.
0: Normal
1: Error
2: Disable
R/W

+195 Consumed_WH_In_Last_Term30 (State)