1 FUNCTIONS
1.1 BACnet Object Function
89
1
BACnet module
■ Operation at startup
At the startup of a BACnet module, the module writes values, which are saved in the internal memory before powering OFF
(or resetting) the module, to the STATUS in the buffer memory.
■ Cyclic operation
A BACnet module periodically
*1
reads a CONTROL in the buffer memory and applies the following processing result to the
internal memory.
*1 For the reading cycle, refer to the following section.
Page 264 Loading buffer memory
*1 When '1' is set to "OutOfServiceControl" in [Settings] [Basic Information] [BACnet Detail Setting] button "Interface", the value of an OutOfService
property is stored. (Page 281 Interface)
START
YES
NO
NO
YES
OutOfServicie=1
Reliability=0
END
Read the CONTROL
Set the read 32-bit integer value to
the PresentValue property
Set the OutOfService property
*1
Set NoFaultDetected to
the Reliability property
Set the read value to
the Reliability property
Set the read value to the following property
・ContractRecivingPower
・TargetValueOfPower
・StartTimeOfMonitoring
・EstimatedPower
・AdjustPower
・ElapsedTime
・TimeWidthOfWHTrend
・ConsumedWHInThisTerm
・ConsumedWHInLastTerm