1 FUNCTIONS
1.1 BACnet Object Function
95
1
Settings using a program
The property values in a BACnet module can be changed by writing values to the buffer memory using a program.
Settings at normal operation
1. Write a value to the PresentValue.
2. Write the CONTROL whose OutOfService and Reliability are '0'. (No writing is required when '0' has already been
written.)
To change an OutOfService property to True
1. Write the CONTROL whose OutOfService is '1' to the buffer memory.
Precautions
When the OutOfService is '1', the PresentValue and the Reliability are not used.
Leave the OutOfService of the CONTROL '1' until the OutOfService of the StatusFlags becomes '1' (1 second or more).
To change an OutOfService property from True to False
1. Write a value to the PresentValue.
2. Write the CONTROL whose OutOfService value is '0' and Reliability value is an appropriate one.
Precautions
When the Reliability is other than '0', writing a value to the PresentValue is unnecessary.
Leave the OutOfService of the CONTROL '0' until the OutOfService of the StatusFlags becomes '0' (1 second or more).
Settings for a Reliability property at error occurrence
1. Write the CONTROL whose OutOfService is '0' and Reliability is other than '0'.
Another setting
Manage the data of the following properties with a program. If any changes are made, write the changed data to the buffer
memory.
Level_Value property