34
1 FUNCTIONS
1.3 Communications Using the Predefined Protocol
Newly creating the protocol setting data
Newly create the protocol setting data.
[File] [New]
Item Description
Protocol No. Displays the protocol number used with the dedicated instruction in the program.
Manufacturer Displays the name of the manufacturer of the device for which the protocol is being set.
Model Displays the model of the protocol to be set.
Protocol Name Displays the name of the protocol to be set.
Communication Type Displays the communication type of the protocol to be set.
Send only: Sends one send packet once.
Receive only: If there is a matching packet within up to 16 registered and received packets, it is received.
Send & receive: After sending one send packet, if there is a matching packet within up to 16 registered and received
packets, it is received.
Send/Receive Displays the packet send direction.
: For send
(1) to (16): For receive, the received packet number is displayed in parentheses.
Packet Name Displays the packet name.
Packet Setting Displays the validity of variables in the packet elements and the variable setting state.
If the variable is not set, there are no elements, or there is an element error, the protocol is not written to the Ethernet-
equipped module.
No Variable: When there is no variable in the elements
Variable Set: Only when all variables have been set
Variable Unset: When there is even one unset variable
Element Unset: When there are no elements in an editable protocol
Element error: When elements do not satisfy requirements