EasyManua.ls Logo

Mitsubishi Electric MELSEC iQ-R08ENCPU - Device Assignment

Mitsubishi Electric MELSEC iQ-R08ENCPU
416 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 PARAMETER SETTINGS
2.3 Application Settings
255
2
Device Assignment
Set the MODBUS device assignment parameters to use the MODBUS device assignment function.
Create the association between the following MODBUS devices and the device memory areas of the CPU module.
•Coil
Input
Input register
Holding register
When "Device" is blank, values set in "Start MODBUS Device No." and "Allocation Points" are ignored.
In this case, data written into the programmable controller will not be assigned to the MODBUS devices.
(When the written data are read from the programmable controller, "Start MODBUS Device No." and
"Allocation Points" are set to 0.)
Item Description
Device Set the devices of the CPU module to be assigned to the MODBUS devices.
Use H to specify a buffer memory area. (Example: H1D5000)
Start MODBUS Device No. Set the start number of the devices of the CPU module to be assigned to the MODBUS devices.
The setting value for the start MODBUS device number can be obtained with the following formula.
Start MODBUS device number = Last five digits of the target MODBUS device number - 1
Allocation Points Set the number of device points of the CPU module to be assigned to the MODBUS devices.

Table of Contents