1 FUNCTIONS
1.1 Connection with MELSOFT Product and GOT
Conditions that cannot communicate with direct connection
Communication with a direct connection may be disabled if the following conditions apply. If connection is not possible, review
the settings for the Ethernet-equipped module and personal computer.
When all bits of the IP address for the Ethernet-equipped module that correspond with the 0 section of the subnet mask for
the personal computer are on or off
Ex.
IP address for the Ethernet-equipped module: 64.64.255.255
IP address for the personal computer: 64.64.1.1
Subnet mask for the personal computer: 255.255.0.0
When all bits of the IP address for the Ethernet-equipped module that correspond with the host address of each class in the
IP address for the personal computer are on or off
Ex.
IP address for the personal computer: 192.168.0.1 192.x.x.x., class C and the host address is the fourth octet.
Subnet mask for the personal computer: 255.0.0.0
IP address for the Ethernet-equipped module: 64.64.255.255 each bit turns on because of the fourth octet is 255
The IP address for each class are as follow.
Class A: 0.x.x.x to 127.x.x.x
Class B: 128.x.x.x to 191.x.x.x
Class C: 192.x.x.x to 223.x.x.x
The host address for each class is the 0 section shown below.
Class A: 255.0.0.0
Class B: 255.255.0.0
Class C: 255.255.255.0