1 FUNCTIONS
1.2 SLMP Communications
27
1
1.2 SLMP Communications
SLMP is a protocol used by external devices to access SLMP-compatible devices via the Ethernet.
SLMP communications are available among devices that can receive/send messages with the SLMP control procedure.
The Ethernet-equipped module processes and transfers data following instructions (command) from the external device, so
the programmable controller only needs the open/close processing and does not require a program for data communication.
For SLMP communications, refer to the following.
SLMP Reference Manual
Applications
This section describes the applications of SLMP communications.
Data read/write
Data read/write can be executed for the following data. With this, the external device can monitor the operation of the
Ethernet-equipped module, analyze data, and control production.
Device or global label of the CPU module connected with the RJ71EN71 (When the Ethernet function of the RJ71EN71 or
the RnENCPU (network part) is used)
Device or global label of the CPU module (When the Ethernet function of the CPU module (CPU part for the RnENCPU) is
used)
Buffer memory of the intelligent function module
File read/write
Files such as parameter files stored in a CPU module can be read/written. Files in a CPU module can be managed on an
external device.
Remote control of a CPU module
A CPU module can be remotely controlled from the external device using remote operations.
Remote password lock/unlock
The remote password can be locked and unlocked from the external device.
Access to the programmable controller on another station via other network
In systems with CC-Link IE Controller Network, CC-Link IE Field Network, MELSECNET/H, MELSECNET/10 or Ethernet, the
programmable controller on another station can be accessed from the external device via the network. However, when
connecting the external device to the CPU module (built-in Ethernet port part), other stations cannot be accessed via network
such as CC-Link IE Controller Network and CC-Link IE Field Network.
Accessing to another station via the port 1 and port 2 of the RJ71EN71 is possible for the module with the
firmware version of "18" or later.