1 FUNCTIONS
1.4 Socket Communications
63
1
Precautions for TCP/IP communications
Conditions for closing
In addition to when close is requested from the external device, the TCP/IP communications processing will be closed in the
following cases if 'Open completion signal' (Un\G1900000 to Un\G1900007) turns off.
When alive check function times out
When forced close is received from external device
TCP/IP connection elements
The TCP/IP connection is managed with the following four elements. Only one connection containing the same four elements
can be created at one time. To use multiple TCP/IP connections simultaneously, ensure that one of the four elements is
different.
IP address of the Ethernet-equipped module side
Port number of the Ethernet-equipped module side
IP address of the external device side
Port number of the external device side
Reconnecting with same connection
After closing the connection during TCP/IP communications, wait at least 500ms before reconnecting to a connection with the
same external device (IP address), own station port number, and external device port number.
If a wait interval cannot be provided before reconnecting, changing the own station port number on the Active open side and
connecting is recommended.