EasyManua.ls Logo

Mitsubishi Electric MELSEC iQ-RJ71C24-R2 - Packet; Packet Elements

Mitsubishi Electric MELSEC iQ-RJ71C24-R2
574 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 DATA COMMUNICATION USING PREDEFINED PROTOCOL
2.3 Packet
35
2
2.3 Packet
A packet consists of packet elements.
Up to 32 elements can be set in a packet, and the maximum data length is 2048 bytes per packet.
Packet elements
The following explains the details of the packet elements.
For data examples on packet elements, refer to the following section.
Page 527 Data examples of packet elements
Header
Use this element when a specific code or character string exists at the head of a packet.
When sending: Sends a specified code and character string.
When receiving: Verifies a header and received data.
Only one header can be used in a packet.
A header can be set only at the head of a packet.
Item Description Remarks
Element Name Set a name of the element.
Code Type Select a data type of the setting value.
ASCII String/ASCII Control Code/HEX
Setting Value Set data within 1 to 50 bytes.
The setting ranges that can be set for each code type are as follows:
ASCII String: 20H to 7EH
ASCII Control Code: 00H to 1FH, and control code of 7FH
HEX: hexadecimal data of 00H to FFH
Setting example
ASCII String: 'ABC'
ASCII Control Code: STX
HEX : FFFF

Table of Contents

Other manuals for Mitsubishi Electric MELSEC iQ-RJ71C24-R2

Related product manuals