7 COMMUNICATIONS BY THE MODEM FUNCTION
7.1 Overview
149
7
Features
The following explains the features of the modem function.
Interface that can use the modem function
The modem function can be used with an RS-232 interface of C24.
For the RJ71C24-R2, the modem function can be used for only one of the two RS-232 interfaces.
With the other interface of C24, direct data communication with a target device can be performed using MC protocol,
nonprocedural protocol, or bidirectional protocol (independent operation).
Initialization/connection/disconnection of modem or TA
The following setting value for line connection can be used by registering in the module extended parameter or flash ROM
of C24 in multiple sets.
Data for Modem/TA initialization (AT command)
User setting: 30 sets (78 bytes/set), default value: 13 sets
Data for connection
User setting: 30 sets (80 bytes/set) (display message to telephone number of the connection destination, line type, etc.)
By registering the above data to C24 in advance, the modem/TA (terminal adapter) initialization, line connection (dialing),
and line disconnection can be performed easily.
When the no-communication interval time (1 min to 120 min) is set, C24 disconnects the line when a no-communication
condition continues for the set period of time following the line connection.
Communication between remote device and CPU module
Data communication can be performed via full-duplex communication.
From the target device to the CPU module, communication using the MC protocol, nonprocedural protocol, or bidirectional
protocol can be performed.
From the CPU module to the target device, communication using the MC protocol (transmission by the on-demand function
only), the nonprocedural protocol, or bidirectional protocol can be performed.
Communication using the modem function
Communication without using the modem function