19 SWITCHING THE MODE AFTER STARTING
19.3 I/O Signals for Handshake with CPU Module and Buffer Memory
381
19
Switching mode No. designation (Un\G144/304)
Write the mode No. after mode switching (0001H to 0007H, 0009H, 00FFH).
When "0000H" is designated, the operation will be matched with the setting in MELSOFT.
*1 Specify "00H" for the communication protocol setting when specifying the MELSOFT connection mode with the parameter settings of
Engineering tool.
Transmission specifications after switching designation (Un\G145/305)
1. Specify the transmission specifications after mode switching.
2. Write "0000H" when returning to the settings configured with Engineering tool.
3. When setting arbitrary transmission specifications (other than the transmission specification set with Engineering tool),
write the value corresponding to ON/OFF of the relevant bit.
*2
The relevant bit 1 (ON)/0 (OFF) is specified as the same
as the transmission setting of Engineering tool.
•For C24
*1 On the side of interface to which "MELSOFT connection" is set for the switching mode No. designation, set all items to the OFF side.
C24 operates with the setting values set with Engineering tool.
Transmission setting Engineering tool side setting
Operation setting Independent
Data bit 8
Parity bit Yes
Odd/even parity Odd
Stop bit 1
Sum check code Yes
Online change Enable
Setting change Enable
b15 b0
to
Buffer memory address
Un\G144/304
(Default 0000H)
0001H : MC protocol (Format 1)
0002H : MC protocol (Format 2)
0003H : MC protocol (Format 3)
0004H : MC protocol (Format 4)
0005H : MC protocol (Format 5)
0006H : Nonprocedural protocol
0007H : Bidirectional protocol
0009H : Predefined protocol
00FFH : MELSOFT connection
*1
15 b7
b6 b5
b4
b3
b2
b1 b0b8
0
b0
b7
b6
b5
b4
b3
b2
b1
78
12
OFF(0) ON(1)
b8
b15
to
CH1 side
*1
CH2 side
*1
Description
Remarks
Bit
Operation
setting
Be sure to set the CH1 side
to OFF(0).
Independent
Link
Data bit
Parity bit is not included.
Parity bit
Vertical parity
No Yes
Valid only when parity bit is
set to Exist.
Odd/Even parity Even
Odd
Stop bit
Sum check code
None Exist
Enable
Online change
Disable
Enable
Disable
Setting modifications
Remarks
Description
Set value
Bit
to
Communication
rate
Refer to *2