382
19 SWITCHING THE MODE AFTER STARTING
19.3 I/O Signals for Handshake with CPU Module and Buffer Memory
*2 It indicates the setting value for the communication speed.
Set "80H" to the interface to which "MELSOFT connection" is set for the switching mode No. designation. The
communication speed set on the Engineering tool side is applied.
Precautions
The following I/O signals for handshake and buffer memories need to be considered on the CPU module side at the time of
mode switching from the target device.
•'CH switching mode' (X6/XD)
'Parameter setting error, mode switching error status' (Un\G515)
Communication speed
(units: bps)
Bit position Communication speed
(units: bps)
Bit position Remarks
b15 to b8 b15 to b8
1200 82H 38400 89H Decrease the communication
speed when data cannot be
communicated normally due
to overrun error, framing
error, etc. in communication
with the target device.
2400 83H 57600 8AH
4800 84H 115200 8BH
9600 85H 230400 8CH
14400 86H - -