27 TROUBLESHOOTING
27.4 Error Code List
7140H
*1
Request data
error
The request exceeded the
limit of processing points
that are predetermined for
each command and
allowed for one
transmission.
A word device was
designated in a bit unit
command.
The requested range
exceeded the end device
number.
(CPU module's last device
number Start device
number + Number of device
points in message sent from
the target device)
PRO Check and correct the
transmission message from
the target device and restart
data communications.
If no error is found in the
device range, clear the
programmable controller CPU
information and retry.
7141H System error The operating system of
C24 detected some error.
Page 490 Corrective actions
for system error
7142H
*1
Device name
error
Device that cannot be
specified by the
corresponding command
was designated.
PRO Check and correct the
transmission message from
the target device and restart
data communications.
If no error is found in the
device name, clear the
programmable controller CPU
information and retry.
7143H
*1
Device No. error The start device number
is out of range.
PRO Check and correct the
transmission message from
the target device and restart
data communications.
7144H
*1
Monitor
registration error
Monitoring was requested
before the monitor
registration has been
performed.
PRO Register the device to be
monitored before issuing a
monitor request.
7145H
*1
Monitor PC No.
error
The registered PC No.
and PC No. in the monitor
request are different.
C/N Check and correct the
transmission message from
the target device and restart
data communications.
Perform the monitor
registration again.
7146H
*1
Monitor CPU
model error
The registered CPU
model name and the CPU
monitor name in the
monitor request are
different.
C/N Check and correct the
transmission message from
the target device and restart
data communications.
Perform the monitor
registration again.
7147H
*1
Number of
monitor
registration point
exceeded error
The number of monitor
registration points
exceeded the range.
PRO Check and correct the
transmission message from
the target device and restart
data communications.
7148H
*1
Extended R block
No. error
A nonexistent extension
file register block No. was
designated.
A block No. being used as
an extension comment
area, sampling trace area,
or status latch area was
designated.
PRO Check and correct the
designated block No. and
restart data communications.
Error code
(hexadecima
l)
Error Description Signal
name
Corrective action Protocol
MC Nonpr
ocedu
ral
Bidire
ctiona
l
Prede
fined

Table of Contents

Other manuals for Mitsubishi Electric MELSEC iQ-RJ71C24-R4

Related product manuals