APPENDICES APPENDIX
Appendix 3 Buffer Memory
511
A
8256
(2040H)
8512
(2140H)
For designation
of
programmable
controller CPU
monitoring
function
Cycle time units designation
0: 100 ms 1: s 2: min
2R Page 138 Settings for
Using the
Programmable
Controller CPU
Monitoring Function
8257
(2041H)
8513
(2141H)
Cycle time designation (programmable
controller CPU monitoring interval time)
0H : No designation
1H to FFFFH: Programmable controller CPU
monitoring interval time
5H
8258
(2042H)
8514
(2142H)
Programmable controller CPU monitoring
function designation
0: Do not use the function.
1: Fixed cycle send
2: Condition match send
0
8259
(2043H)
8515
(2143H)
System area
8260
(2044H)
8516
(2144H)
Send pointer designation (For fixed cycle send
and nonprocedural data transmission)
0: No specification
1 to 100: Output head point (send from the nth)
Send the user frames designated in the
following send frame number designation areas
from the designated pointer position.
(addresses: CH1 side = BAH to 11DH, CH2
side = 15AH to 1BDH)
0 R
8261
(2045H)
8517
(2145H)
Output quantity designation (for fixed cycle
send and nonprocedural data transmission)
0: No specification
1 to 100:Output quantity (Specify the number of
frame to be transmitted.)
0
8262
(2046H)
8518
(2146H)
Data No. for connection designation (for fixed
cycle send)
0: No designation
0BB8H to 0BD5H, 8001H to 801FH: Data No.
for connection
0R
8263 to
8268
(2047H to
204CH)
8519 to
8524
(2147H to
214CH)
Use prohibited System area
8269
(204DH)
8525
(214DH)
For designation
of
programmable
controller CPU
monitoring
function
Registered word block quantity designation
0: No designation
1 to 10: Number of blocks of word devices
(Up to 10 blocks can be designated in total.)
0R Page 138 Settings for
Using the
Programmable
Controller CPU
Monitoring Function
8270
(204EH)
852
6
(214EH)
Registered bit block quantity designation
0: No designation
1 to 10: Number of blocks of bit devices
(Up to 10 blocks can be designated in total.)
0
8271
(204FH)
8527
(214FH)
CPU error monitoring designation
0: Do not monitor. 1: Monitor.
0
8272
(2050H)
8528
(2150H)
1st block monitoring device
Monitoring device designation
0: No designation
90H to CCH: Device code
0
8273,
8274
(2051H,
2052H)
8529,
8530
(2151H,
2152H)
1st block monitoring device
Start device No. specification
0 or more: Start device number
0
8275
(2053H)
8531
(2153H)
1st block monitoring device
Number of read points specification
0: No specification
1 or more: read point
0
8276
(2054H)
8532
(2154H)
1st block monitoring device
Monitoring condition specification (judgment
condition specification)
0: No specification
1 or more: Monitoring condition
0
Address
Dec (Hex)
Purpose Name Defaul
t value
Protocol Reference
CH1 CH2 MC Non Bi Pd