APPENDICES APPENDIX
Appendix 5 Operation Image and Data Structure of Predefined Protocol
539
A
Data flow: Reverse direction
"No Complement Calculation" is designated (1B0H in hexadecimal is 432 in decimal)
*1 Values in '( )' indicate ASCII code.
"One's complement" is designated (One's complement for 0000 01B0H is FFFF FE4FH)
When "Code type" is "ASCII decimal", the lower one word is extracted and converted from hexadecimal to decimal. (FE4FH
in hexadecimal is 65103 in decimal.)
*1 Values in '( )' indicate ASCII code.
"Two's complement" is designated (Two's complement for 0000 01B0H is FFFF FE50H)
When "Code type" is "ASCII decimal", the lower one word is extracted and converted from hexadecimal to decimal. (FE50H
in hexadecimal is 65104 in decimal.)
*1 Values in '( )' indicate ASCII code.
Code type Data length
*1
1 byte 2 bytes 3 bytes 4 bytes
ASCII hexadecimal "0B" (30H 42H) "0B1" (30H 42H 31H) "0B10" (30H 42H 31H 30H)
ASCII decimal "23" (32H 33H) "234" (32H 33H 34H) "2340" (32H 33H 34H 30H)
HEX B001H B00100H B0010000H
Code type Data length
*1
1 byte 2 bytes 3 bytes 4 bytes
ASCII hexadecimal "F4" (46H 34H) "F4E" (46H 34H 45H) "F4EF" (46H 34H 45H 46H)
ASCII decimal "30" (33H 30H) "301" (33H 30H 31H) "3015" (33H 30H 31H 35H)
HEX 4FFEH 4FFEFFH 4FFEFFFFH
Code type Data length
*1
1 byte 2 bytes 3 bytes 4 bytes
ASCII hexadecimal "05" (30H 35H) "05E" (30H 35H 45H) "05EF" (30H 35H 45H 46H)
ASCII decimal "40" (34H 30H) "401" (34H 30H 31H) "4015" (34H 30H34H 35H)
HEX 50FEH 50FEFFH 50FEFFFFH