5 TROUBLESHOOTING
5.6 List of Error Codes
2450H • A major error notification from the RJ71EIP91 has
been detected.
• The I/O module or RJ71EIP91 is not mounted
properly or was removed during operation.
• Take measures to reduce noise.
• Check the connection status of the extension cable.
• Check the detailed information (system
configuration information) by executing module
diagnostics using the engineering tool, and check
the module corresponding to the displayed slot
number.
• Reset the CPU module, and then switch it to RUN
mode. If the error occurs again even after the above
action is taken, the possible cause is a hardware
failure of the module on which the error occurred.
Please consult your local Mitsubishi representative.
System configuration
information
• I/O number
• Base number
•Slot number
24C0H to
24C1H
An error was detected on the system bus. • Take measures to reduce noise.
• Reset the CPU module, and then switch it to RUN
mode. If the error occurs again even after the above
action is taken, the possible cause is a hardware
failure of the CPU module, I/O module, RJ71EIP91,
base unit, or extension cable. Please consult your
local Mitsubishi representative.
System configuration
information
• I/O number
• Base number
•Slot number
•CPU number
24C2H • The I/O module or RJ71EIP91 is not mounted
properly or was removed during operation.
• An error was detected on the system bus.
• Check the detailed information (system
configuration information), and check the module
corresponding to the displayed slot number.
• Check the connection status of the extension cable.
• Take measures to reduce noise.
• Reset the CPU module, and then switch it to RUN
mode. If the error occurs again even after the above
action is taken, the possible cause is a hardware
failure of the CPU module, I/O module, RJ71EIP91,
base unit, or extension cable. Please consult your
local Mitsubishi representative.
System configuration
information
• I/O number
• Base number
•Slot number
•CPU number
24C3H An error was detected on the system bus. • Take measures to reduce noise.
• Reset the CPU module, and then switch it to RUN
mode. If the error occurs again even after the above
action is taken, the possible cause is a hardware
failure of the CPU module, I/O module, RJ71EIP91,
base unit, or extension cable. Please consult your
local Mitsubishi representative.
System configuration
information
• I/O number
• Base number
•Slot number
•CPU number
24C4H An error was detected on the system bus. • Take measures to reduce noise.
• Reset the CPU module, and then switch it to RUN
mode. If the error occurs again even after the above
action is taken, the possible cause is a hardware
failure of the CPU module, I/O module, RJ71EIP91,
base unit, or extension cable. Please consult your
local Mitsubishi representative.
System configuration
information
• I/O number
• Base number
•Slot number
24C5H An error was detected on the system bus. • Take measures to reduce noise.
• Reset the CPU module, and then switch it to RUN
mode. If the error occurs again even after the above
action is taken, the possible cause is a hardware
failure of the I/O module, RJ71EIP91, base unit, or
extension cable. Please consult your local
Mitsubishi representative.
24C6H An error was detected on the system bus. • Take measures to reduce noise.
• Reset the CPU module, and then switch it to RUN
mode. If the error occurs again even after the above
action is taken, the possible cause is a hardware
failure of the CPU module or extension cable.
Please consult your local Mitsubishi representative.
24C8H An error was detected on the system bus. • Take measures to reduce noise.
• Reset the CPU module, and then switch it to RUN
mode. If the error occurs again even after the above
action is taken, the possible cause is a hardware
failure of the I/O module, RJ71EIP91, or extension
cable. Please consult your local Mitsubishi
representative.
Error
code
Error details and causes Action Detailed information