5 TROUBLESHOOTING
5.6 List of Error Codes
127
5
Error codes when a communication error occurs
Error codes for communication errors can be checked with 'Class1 Connection Behavior Error status' (Un\G27392 to
Un\G27647). ( Page 151 Class1 Connection Behavior Error status (Un\G27392 to Un\G27647))
Error code Error details and causes Action
102H EtherNet/IP communication has not started properly. When UCMM communications are performed, check whether a
module error occurs in the following pages.
Page 110 Checking with LEDs
Take measures to reduce noise.
Reset the CPU module, and then switch it to RUN mode. If the
error occurs again even after the above action is taken, the
possible cause is a hardware failure of the module. Please
consult your local Mitsubishi representative.
103H A parameter error was detected. Use EtherNet/IP Configuration Tool to write the parameters to
the module again.
When UCMM communications are performed, check whether
the setting details of the UCMM request area are correct.
104H to 105H A timeout occurred in the connection with the external device. Check whether the operating status of the external device is
normal.
Check for errors in the line status.
The line may be busy, so retry at a later time.
The external device may not be able to send data at the
specified RPI due to a high communication load, so specify a
larger RPI and connect again.
Check the settings of the connection with the external device.
When Application Trigger is used, check whether the data send
timing is correct.
106H The target device does not exist. Use EtherNet/IP Configuration Tool to write the parameters to
the module again.
If the error occurs again even after the above action is taken,
the possible cause is a hardware failure of the module on which
the error occurred. Please consult your local Mitsubishi
representative.
107H An error was detected in the memory. Take measures to reduce noise.
Reset the CPU module, and then switch it to RUN mode. If the
error occurs again even after the above action is taken, the
possible cause is a hardware failure of the module on which the
error occurred. Please consult your local Mitsubishi
representative.
10AH Production processing failed to start. Take measures to reduce noise.
Reset the CPU module, and then switch it to RUN mode. If the
error occurs again even after the above action is taken, the
possible cause is a hardware failure of the module on which the
error occurred. Please consult your local Mitsubishi
representative.
10BH Consumption processing failed to start. Take measures to reduce noise.
Reset the CPU module, and then switch it to RUN mode. If the
error occurs again even after the above action is taken, the
possible cause is a hardware failure of the module on which the
error occurred. Please consult your local Mitsubishi
representative.
10CH There is insufficient memory available for connection
processing.
Retry at a later time.
Reset the CPU module, and then switch it to RUN mode. If the
error occurs again even after the above action is taken, the
possible cause is a hardware failure of the module on which the
error occurred. Please consult your local Mitsubishi
representative.