3 EtherNet/IP Configuration Tool
3.1 Window Structure
63
3
*1 To perform message communications on products other than the RJ71EIP91, refer to the manual of the product used.
*2 This item is displayed when "Advanced Mode" is selected. ( Page 50 File)
*3 Large Forward Open is used when the size of data to be sent/received is 512 bytes or more.
*4 Forward Open is used when the size of data to be sent/received is 511 bytes or less.
Messaging Selects the communication method.
Connected: Class3 communications
Unconnected: UCMM communications
When selecting "Connected", select whether to use "Large Forward Open".
Selected: Performs Class3 communications using Large Forward
Open.
*3
Not selected: Performs Class3 communications using Forward Open.
*4
Connected
Unconnected
(Default: Unconnected)
Receive Displays the response data from the EtherNet/IP device.
The response data is the data excluding the first four bytes including the
CIP service code and the status code.
Status Displays the communication result. For details, refer to the manuals of the
EtherNet/IP device.
Item Description Setting range