2 PARAMETER SETTINGS
2.4 Application Settings
153
2
Setting items
Item Description Setting range
Setting Method Right-click in the "Safety Communication Setting" window and
select an assignment method in "Safety Data Transfer Device
Setting".
• Start/End: Enter the start and end numbers of safety
devices.
• Points/Start: Enter the points and start numbers of safety
devices.
• Start/End
• Points/Start
(Default: Start/End)
No. Safety connection number for distinguishing settings for each
safety connection.
1 to 120
*1
Communication Destination Set a network of the communication destination. Local Network
(Default: Blank)
Network Configuration Network No. Displays the local network number.
Station No. • When the own station is the master station: The station
number of communication destination selected in "Select
the target module for the Safety Communication Setting"
window is displayed.
• When the own station is a local station: Set the station
number of communication destination.
• When the own station is the master
station:
• When the own station is a local
station: 0 to 120
(Default: Blank)
Station Type When the own station is the master station, the station type of
the communication destination selected in "Select the target
module for the Safety Communication Setting" window is
displayed.
Configured Module Base No.
*2
When the own station is the master station, the base number
of the communication destination selected in "Select the
target module for the Safety Communication Setting" window
is displayed. (For the intelligent device station only)
Mounting slot number
*2
When the own station is the master station, the mounting slot
number of the communication destination selected in "Select
the target module for the Safety Communication Setting"
window is displayed. (For the intelligent device station only)
Model Name When the own station is the master station, the module model
name of the communication destination selected in "Select
the target module for the Safety Communication Setting"
window is displayed. (Only slave station other than the local
station)
Communication
Destination
In the following cases, set the Safety CPU model name of the
communication destination. (Only when the Safety CPU is
used)
• When the own station is a master station: When the
communication destination is a local station and the open
system of the own station is Active
• When the own station is a local station: When the open
system of the own station is Active
•R08SFCPU
•R16SFCPU
•R32SFCPU
• R120SFCPU
(Default: Blank)
Open System
*3
Set the open system of the own station.
• Active: Safety connections are established from the own
station.
• Passive: Safety connections are established from the
communication destination.
• Active
• Passive
(Default: Blank)
Sending Interval Monitoring Time [ms] In each safety connection, set sending interval monitoring
time for a receiving station to detect safety communication
errors.
■When the Safety CPU is used
3.0 to 1000.0
(Default: Blank)
■When the SIL2 Process CPU is used
30.0 to 3000.0
(Default: Blank)
Safety Refresh Monitoring Time [ms] In each safety connection, set safety refresh monitoring time
for a receiving station to detect safety communication errors.
Set this item for the Active side of the safety stations that
perform safety communications.
■When the Safety CPU is used
4.0 to 2000.0
(Default: Blank)
■When the SIL2 Process CPU is used
40.0 to 6000.0
(Default: Blank)