2 PARAMETER SETTINGS
2.4 Application Settings
*1 Set the safety connection number starting with 1.
Even if the safety connection is set in a random line, the unset line is deleted and the number is set starting with 1 when the [OK] button
is clicked.
*2 This item is displayed only for a project of the SIL2 Process CPU.
*3 This item is fixed to "Active" when the communication destination is an intelligent device station.
*4 For a project of the SIL2 Process CPU, the output module with diagnostic functions cannot be set.
*5 For a project of the SIL2 Process CPU, the input module with diagnostic functions cannot be set.
Redundant System Settings
Set the redundant system function.
Safety Data Transfer
Device Setting
Receive Data Storage
Device
*4
Set a safety device of the SIL2 Process CPU and the Safety
CPU where safety data are stored.
Device Name
SA\X
SA\M
SA\B
SA\D
SA\W
(Default: Blank)
Points
Bit device: 16 to 128 (set in
increments of 16 points)
Word device: 1 to 8 (set in
increments of 1 point)
(Default: Blank)
Start/End
Range of a safety device in the SIL2
Process CPU and the Safety CPU
(Default: Blank)
Send Data Storage
Device
*5
Set a safety device of the SIL2 Process CPU and the Safety
CPU where safety data are sent.
Device Name
SA\Y
SA\M
SA\B
SA\D
SA\W
(Default: Blank)
Points
Bit device: 16 to 128 (set in
increments of 16 points)
Word device: 1 to 8 (set in
increments of 1 point)
(Default: Blank)
Start/End
Range of a safety device in the SIL2
Process CPU and the Safety CPU
(Default: Blank)
[Output to File (for Setting Confirmation)] button Outputs the contents of the safety communication setting to a
CSV file.
The file is used to check whether there is no discrepancy
between the safety communication setting written to the
Safety CPU and that of the project. ( GX Works3
Operating Manual)
Item Description Setting range
Station No. (System
A)
Displays the station number set in "Station No." under "Required Settings".
Module Operation
Mode (System A)
Displays the module operation mode set for "Module Operation Mode" under "Application Settings".
Station No. (System
B)
Displays the station number of system B.
Module Operation
Mode (System B)
Set the module operation mode of system B.
For details on the module operation mode, refer to the following.
Page 147 Module Operation Mode
Online
Offline
Module
Communication Test
(Default: Online)
Item Description Setting range