4 TROUBLESHOOTING
4.7 Event List
279
4
4.7 Event List
This section lists the events which occur in CC-Link IE Field Network.
System and operation are included in the event types.
System
Event code Overview Cause
00100 Link-up Link-up has occurred when the network cable connected to the external device
was connected.
00130 Receive frame error Receive frame error was detected. Or, the network whose network type is
different was connected.
00500 <<Own station>> Baton pass return (network entry) Baton pass of the own station was returned from interruption status to normal
status.
00501 <<Another station>> Baton pass return (network entry) Baton pass of another station was returned from interruption status to normal
status.
00502 All stations baton pass normalization (network entry in all
stations)
Baton pass was returned to normal status at all stations.
00510 <<Own station>> Data link restart (cyclic transmission
started)
Data link of the own station was restarted.
00511 <<Another station>> Data link restart (cyclic transmission
started)
Data link of another station was restarted.
00512 All stations data link normalization (cyclic transmission in
all stations started)
Data link was returned to normal status at all stations.
00513 <<Own station>> Data link start instruction acceptance Data link startup of the own station instruction was received.
00514 <<Own station>> Data link stop instruction acceptance Data link stop instruction of the own station was received.
00520 <<Own station>> Temporary error invalid station setting
instruction acceptance
Temporary error invalid station setting instruction was received.
00521 <<Own station>> Temporary error invalid station cancel
instruction acceptance
Temporary error invalid station cancel instruction was received.
00524 <<Another station>> Temporary error invalid station setting
execution
Temporary error invalid station was set at another station.
00525 <<Another station>> Temporary error invalid station cancel
execution
Temporary error invalid station was canceled at another station.
00530 <<Own station>> Reserved station cancel setting
instruction acceptance
Reserved station cancel setting instruction was received.
00531 <<Own station>> Reserved station enable setting
instruction acceptance
Reserved station enable setting instruction was received.
00534 <<Another station>> Reserved station cancel setting
execution
Reserved station cancel setting was executed at another station.
00535 <<Another station>> Reserved station enable setting
instruction execution
Reserved station enable setting was executed at another station.
00540 Loopback resolution Loopback execution status was resolved when using a ring topology (using the
loopback function).
00541 Receive parameter error resolution A parameter error received from master station/control station was resolved.
(Normal parameter was received.)
00542 <<Own station>> Receive frame error line status caution
level
A receive frame error (line status: caution level) has been occurred.
00543 <<Another station>> Receive frame error line status
caution level
A receive frame error (line status: caution level) has been occurred.
00600 <<Own station>> Master/submaster switching occurrence Master station down, or manual switching of the master and submaster station
has occurred.
00800 Link-down Link-down occurred when network cable connected to the external device was
disconnected.
00A00 System switching request issued A system switching request occurred.
00C00 <<Own station>> Baton pass interruption (departure from
network)
Baton pass of the own station was interrupted.
00C01 <<Another station>> Baton pass interruption (departure
from network)
Baton pass of another station was interrupted.