88
1 FUNCTIONS
1.7 Redundant System Function
Precautions
Tracking
Of all refresh target devices of link devices (RY, RWw), tracking needs to be set for the devices in the own station send
range.
Tracking cannot be set for link direct devices.
Do not set tracking for the link special relay areas (SB0020 to SB01FF), which are turned on/off by the system, or the link
special register areas (SW0020 to SW01FF), where data is stored by the system.
For details on tracking, refer to the following.
MELSEC iQ-R CPU Module User's Manual (Application)
Operation after return
When the RJ71GF11-T2 is disconnected due to a communication error, switched from the control system to the standby
system through system switching, and returns, system switching does not occur and it returns as the standby system.
Cyclic transmission
Depending on the error status of the control system CPU module, the cyclic data is not sent from the control system
RJ71GF11-T2.
System status of the slave station in a redundant line configuration
Depending on the error status of the control system CPU module, the slave station connected to the control system network
operates in the standby system.