9 CREATING A HARDWARE LOGIC
9.1 Main Blocks in the Hardware Logic Outline Window
109
9
Y device terminal
In the first section in the hardware logic outline window, 16 Y device terminals ("Y 10" to "Y 1F") are arranged by default.
The ON/OFF states of General command 0 to General command F (Y10 to Y1F) are output as signals and used as inputs in
the hardware logic. Select ON or OFF of General command 0 to General command F (Y10 to Y1F) with a program.
Output
The following table shows the output of the Y device terminal.
*1 A logical operation block can be linked only when an OUT terminal is not linked to the logical operation block.
The timing of when signals output from Y device terminals are input to the link destination input terminal may
delay due to the scan time or other causes. To input the signals to multiple connection destinations at the
same time, using an external input block to which an external input signal is assigned is recommended.
For details on the external input block, refer to the following.
Page 106 External input block
To use the flexible high-speed I/O control module as an output module, link blocks in the hardware logic
outline window as shown below.
Variable name Data type Linkable block Output value Description
Input Bit • Multi function counter
• Logical operation
*1
0, 1 Outputs the ON/OFF states of General command 0 to
General command F (Y10 to Y1F) as signals.
Y 10
AND
OUT 0
Logic_Operation