140
9 CREATING A HARDWARE LOGIC
9.2 Multi Function Counter Block
Pulse input modes and count timing
The following table shows the relationships between each pulse input mode and count timing.
"Pulse Input Mode" Count timing
1-phase multiple of 1 (1-Phase Multiple of 1+, 1-
Phase Multiple of 1-)
At up count The value is counted up at the rise () of ΦA.
ΦB is Low.
At down count The value is counted down at the fall () of ΦA.
ΦB is High.
1-phase multiple of 2 (1-Phase Multiple of 2+, 1-
Phase Multiple of 2-)
At up count The value is counted up at the rise () and fall () of
ΦA.
ΦB is Low.
At down count The value is counted down at the rise () and fall ()
of ΦA.
ΦB is High.
CW/CCW (CW/CCW+, CW/CCW-) At up count The value is counted up at the rise () of ΦA.
ΦB is Low.
At down count ΦA is Low.
The value is counted down at the rise () of ΦB.
2-phase multiple of 1 (2-Phase Multiple of 1+, 2-
Phase Multiple of 1-)
At up count When ΦB is Low, the value is counted up at the rise
() of ΦA.
At down count When ΦB is Low, the value is counted down at the
fall () of ΦA.
2-phase multiple of 2 (2-Phase Multiple of 2+, 2-
Phase Multiple of 2-)
At up count When ΦB is Low, the value is counted up at the rise
() of ΦA.
When ΦB is High, the value is counted up at the fall
() of ΦA.
At down count When ΦB is High, the value is counted down at the
rise () of ΦA.
When ΦB is Low, the value is counted down at the
fall () of ΦA.
2-
phase multiple of 4 (2-Phase Multiple of 4+, 2-
Phase Multiple of 4-)
At up count When ΦB is Low, the value is counted up at the rise
() of ΦA.
When ΦA is High, the value is counted up at the rise
() of ΦB.
When ΦB is High, the value is counted up at the fall
() of ΦA.
When ΦA is Low, the value is counted up at the fall
() of ΦB.
At down count When ΦA is Low, the value is counted down at the
rise () of ΦB.
When ΦB is High, the value is counted down at the
rise () of ΦA.
When ΦA is High, the value is counted down at the
fall () of ΦB.
When ΦB is Low, the value is counted down at the
fall () of ΦA.
ΦA
ΦB
ΦA
ΦB
ΦA
ΦB
ΦA
ΦB
ΦA
ΦB
ΦA
ΦB
ΦA
ΦB
ΦA
ΦB
ΦA
ΦB
ΦA
ΦB
ΦA
ΦB
ΦA
ΦB