10 BLOCK LINK EXAMPLES
10.6 Fixed Cycle Output
191
10
■Multi function counter block detail window
*1 Cycle time = (Upper limit value - Lower limit value) × Clock cycle
*2 In the addition mode, the cycle time calculated from the following is applied.
Cycle time = (Upper limit value - Lower limit value) ÷ Addition value × Clock cycle
However, when the count value and the setting value of Step No. 0 do not match each other with the set addition value, fixed cycle
pulses are not output.
The items other than the above need not to be set.
Block Variable name Setting value Description
Input 0
Input 1
Event 0
Event 1
Input_Signal_Event Detector Select User Setting
(ON only in A: Rise)
Set conditions to detect a fixed cycle output start
signal.
Detector Select User Setting
(ON only in B: Rise)
Set conditions to detect a fixed cycle output stop
signal.
Counter_Timer_0 Count Enable ON Set this parameter to "ON".
Count Mode Ring Set this parameter to "Ring".
Upper Limit 1000 Set this parameter according to the control.
*1
Lower Limit 0 Set this parameter according to the control.
*1
Clock 1ms Set this parameter according to the control.
*1
Add Mode OFF Set this parameter according to the control.
*2
Add Value 0
STOP → PRESET ON Set this parameter to "ON", to perform a preset when
a stop event occurs.
Preset Value 0 Set the same value as that in "Lower Limit".
Cam Switch Number of Step 1 Set "1" to enable the step No. 0.
Lower Limit Output State Low Set this parameter to "Low".
Step No.0 999 Set a value of "Upper limit value of the counter timer
block - 1".
Cam Output