204
11 SETTINGS
11.1 Adding the Module
11 SETTINGS
This chapter describes the setting methods for the flexible high-speed I/O control module.
To enable the settings of adding a new module and auto refresh, write the changed settings in the CPU
module, and reset the CPU module, set the RUN/STOP/RESET switch from STOP to RUN twice, or turn off
and on the power.
To enable the switch setting, write the changed setting in the CPU module, and reset the CPU module or
turn off and on the power.
11.1 Adding the Module
Add the model name of the flexible high-speed I/O control module used in the project.
Addition method
Add the model name in "New Module".
[Project window] [Intelligent Function Module] Right-click [New Module]
Item Description
Module Selection Module Type Set "Counter Module".
Module Name Set the module model name to be connected.
Mount Position Mounted Slot No. Set a slot number where the target module is connected.
Specify start XY address The start I/O number (hexadecimal) of the target module is set according to the slot number
where the module is connected. An arbitrary number can also be set.
Title setting Title Set any title.