12 DISPLAY UNIT
12.2 Checking and Clearing Errors
209
12
Clearing errors
Clear errors by eliminating error causes and turning on and off Error clear request (YF) in "DEV MON/TEST".
Ex.
When an error has occurred in the flexible high-speed I/O control module with the start I/O number 10
"CPU MON/TES" window
1. Select "DEV MON/TEST" with the and buttons,
and press the button.
Device selection window
2. Select Y as a target device with the and buttons,
and press the button.
"DEVICE No. SET" window
3. Set the target device to Error clear request (Y1F), and
press the button.
Device monitor window
4. Press the button.
"DEVICE TEST" window
5. Turn on the device with the and buttons.
"DEVICE TEST" window
6. Press the button.
OK
OK
OK
OK
OK