302
Item Description
Display Format Switches the input format of "H/W LED Information" and "H/W SW Information".
H/W LED
Information
INIT.
Indicates the statuses of the LEDs on the E71.
0000: Off
0001: On
OPEN
ERR.
COM. ERR.
BUF1 to
BUF16
Indicates the connection statuses of the connection numbers 1 to 16.
0000: Open not completed
0001: Open completed
H/W SW
Information
NET NO. Indicates the network No. of the E71.
GRP NO. Indicates the group No. of the E71.
ST NO. Indicates the station number of the E71.
MODE
Indicates the mode of the E71.
0000: Online
0001: Offline
0002: Self-loopback test
0003: H/W test
CONFIG
Indicates the operating status of the E71, which has been set with a programming tool.
b0b15 b9 b8 b7 b6 b5 b4 b3 b2 b1
―1/01/0―1/0―― 1/0 1/01/0
6) 5) 4) 3) 2) 1)
1) Communication data code setting
0: Communications in a binary code
1: Communications in an ASCII code
2) Initial/open method setting
0: No parameter setting
(start up according to the sequence program)
1: Parameter setting
(start up according to the parameters)
3) TCP Existence confirmation setting
0: Use the Ping
1: Use the KeepAlive
4) Send frame setting
0: Ethernet frame
1: IEEE 802.3 frame
5) Setting of write enable/disable at RUN time
0: Disable
1: Enable
6) Initial timing setting
0: Do not wait for OPEN
(Communications impossible at STOP time)
1: Always wait for OPEN
(Communication possible at STOP time)