Loading...
103
CHAPTER 4 FUNCTIONS
4
4.2 Transient Transmission Function
4.2.3 Routing function
4.2.3 Routing function
This function allows transient transmissions to stations located on other networks in a multi-network system.
By setting a routing parameter for a relay station on the own network, transient data can be sent to another network
through the relay station. ( Page 238, Section 6.9)
(1) Operation of the routing function
Ex.
When transient data are sent from the request source (1N
S
3) to the request target (3N
S
4)
Relay
station
1
Relay
station
2
Request
target
Request
source
Station Transient transmission (request) Transient transmission (response)
341
Target
network No.
Relay
network No.
Relay
station No.
Passes data to relay station 1NS4 on its
own network to reach network No.3.
342
Target
network No.
Relay
network No.
Relay
station No.
Passes the data to relay station 2NS4
to reach network No.3.
Passes the data to 3N
S4 on network
No.3.
112
Target
network No.
Relay
network No.
Relay
station No.
Passes the data to relay station 2MP1
to reach network No.1
Passes the data to 1N
S3 on network
No.1.
Automatically gives data to the relay
station.
Network No.1
1MP1 1NS2
1NS6 1NS5 1NS4 2MP1
1NS3
(Request source)
Network No.3
3NS2
3NS33NS4
3MP1
(Request target)
(Relay station 1)
2NS4 3NS5
(Relay station 2)
Network No.2
2NS2
1NS3 1NS3
3NS4
1NS4
2MP1
2NS3
1NS4
2MP1
2NS4
3NS5
2NS4
3NS5

Table of Contents