CHAPTER 6 PARAMETER SETTING
6
6.2 Network Settings
(1) Network Type
Select the station type of the CC-Link IE Controller Network module.
When the extended mode is selected using GX Works2, send points can be extended.
For a Basic model QCPU or safety CPU, it is fixed to "CC IE Control (Normal Station)".
To use the extended mode, set a control station and a normal station in the same network to the extended mode.
The same network cannot contain different network types.
(2) Starting I/O No.
Set the start I/O number of the CC-Link IE Controller Network module in 16-point units.
(Setting range: 0000
H
to 0FE0
H
, Default: None)
(3) Network No.
Set a network No. of the network to which the CC-Link IE Controller Network module is connected. (Setting
range: 1 to 239, Default: None)
When multiple network modules and/or Ethernet modules are mounted for one programmable controller, set different
network Nos. for them.
(4) Total Stations
When a control station is selected in "Network Type", set the total number of stations in one network.
(Setting range for Universal model QCPU: 2 to 120, Default: None)
(Setting range for other than Universal model QCPU: 2 to 64, Default: None)
(5) Group No.
Set a group No. for performing transient transmission by group specification. ( Page 102, Section 4.2.2)
(Setting range: 1 to 32, Default: 0 (No group specification))
Item Description
CC IE Control (Control Station)
Set this for the CC-Link IE Controller Network control station.
(One control station is needed for a single network.)
CC IE Control (Normal Station) Set this for the CC-Link IE Controller Network normal station.
CC IE Control Ext. Mode (Control Station)
Set this for a control station where send points can be extended. (GX
Works2 only)
CC IE Control Ext. Mode (Normal Station)
Set this for a normal station where send points can be extended. (GX
Works2 only)