240
(2) Precautions
(a) Transient transmission range
Communication can be made with a station on the eighth farthest network system. (No. of relay stations: 7)
(b) Access conditions when the station No. of the request source, request target or CC-
Link IE Controller Network relay station is 65 or more.
When the station number of the request source or request destination is 65 or more, access can be made
under the following conditions.
• The request source and target are Universal model QCPUs.
• The CC-Link IE Controller Network relay station is a Universal model QCPU.
When the CC-Link IE Controller Network relay station No. is 65 or more, access is available under the following
conditions.
• The request source is a Universal model QCPU.
• The CC-Link IE Controller Network relay station is a Universal model QCPU.
1MP11NS64
1N
S651NS120
2M
P12NS64
Universal model QCPU
Programming tool
CC-Link IE Controller Network MELSECNET/H, etc.
(Request target)(Relay station)
(Request source)
1MP1
2N
S64
1N
S64
Universal model QCPU
Programming tool
CC-Link IE Controller Network MELSECNET/H, etc.
(Request target)
(Relay station)
(Request source)
1N
S65 2MP1
1N
S120