398
• Devices used by the user
(c) REQ instruction settings
• Control data
• Request data
Device Description Device Description
M140 Control and request data setting command
D310 to
D327
Control data
M141 Start contact
D330 to
D335
Request data
M145 Completion device
D340 to
D341
Response data
M146 Completion status indication device D608 Error code storage device
Device Item Set value
(S1)+0 D310 Error completion type
0091
H
(Clock data at the time of error
completion is set.)
(S1)+1 D311 Completion status
—
(Set by the system, no setting required)
(S1)+2 D312 Channel used by own station 5
(S1)+3 D313 Target station's CPU type
0000
H
(Control CPU)
(S1)+4 D314 Target station network No. 1
(S1)+5 D315 Target station No.
FF
H
(All stations)
(S1)+6 D316 (Unused) 0
(S1)+7 D317 Number of resends 5 times
(S1)+8 D318 Arrival monitoring time 0 (10 seconds)
(S1)+9 D319 Request data length 6 (Clock data write)
(S1)+10 D320 Response data length
—
(Set by the system, no setting required)
(S1)+11 D321 Clock set flag
(S1)+12
to
(S1)+15
D322 to D325 Clock data on error completion
(S1)+16 D326 Error-detected network No.
(S1)+17 D327 Error-detected station No.
Device Item Set value
(S2)+0 D330 Request type
0031
H
(Clock data write (when all stations or a group
is specified in (S1)+5))
(S2)+1 D331 Sub-request type
0001
H
(Clock data write)
(S2)+2 D332
Change pattern, clock data to be
changed
0038
H
(Change hour, minute or second.)
(S2)+3 D333
Clock data to be changed
0000
H
(Day, month (No setting))
(S2)+4 D334
3008
H
(Minute, hour (8:30))
(S2)+5 D335
0000
H
(Day of week (No setting), second (00