476
9.18 Z(P).UINI (Station No. Setting of Own Station)
For Universal model QCPUs, the station No. of a normal station (own station) can be set. ( Page 136, Section
4.6)
For use of the UINI instruction, select "Specify Station No. by Program" in the network parameters. ( Page 180,
Section 6.2)
*1 " " (double quotation) of the first argument can be omitted.
(1) Setting data
*1 Local devices and file registers for each program cannot be used as devices in setting data.
Setting
data
Available devices
Internal device
(System, User)
File
register
R, ZR
Link direct
device J\
Intelligent
function
module device
U\G
Index
register Zn
Constant
Others
Bit Word Bit Word K, H $
(S1) — —
(D1) —
Setting data
*1
Description Data type
"Un"/Un
Start I/O number of the own station's CC-Link IE Controller Network module
(00 to FE
H
: The higher two digits of the 3-digit I/O number)
String/
Binary 16 bits
(S1)
Start device of the own station that stores control data
( Page 477, Section 9.18 (2))
Device name
(D1)
The own station's device that is turned on for one scan upon completion of the
instruction
(D1)+1 also turns ON if the instruction execution has failed.
Bit
Z.UINI "Un"
*1
*1
(S1) (D1)
ZP.UINI "Un" (S1) (D1)
Z.UINI
Start contact
[Instruction format][Execution condition][Instruction symbol]
ZP.UINI
Start contact