9.18 Z(P).UINI (Station No. Setting of Own Station)
(2) Control data
*1 The setting side is as shown below.
User: Before execution of the link dedicated instruction, data must be set by the user.
System: The CPU module stores the execution result of the link dedicated instruction.
The UINI instruction can be executed only once.
Once a station No. has been set up, the UINI instruction cannot be executed again. (Doing so will result in error completion.)
In the case of error completion of the UINI instruction, take corrective actions against the error and execute the UINI
instruction again.
Modules are initialized by executing the UINI instruction.
Therefore, cable disconnection is detected in adjacent stations. This may increase IN-side cable disconnection detection
counts (SW0074) or OUT-side cable disconnection detection counts (SW0084).
(3) Function
(a) UINI instruction overview
This instruction sets the station No. of the normal station (own station) that is specified in Un.
Upon completion of the station No. setting, Completion device (D1) turns ON.
Device Item Setting data Setting range
Setting
side
*1
(S1)+0 — Unused 0 User
(S1)+1 Completion status
The instruction completion status is stored.
0: Normal
Other than 0: Error ( Page 511, Section 10.2)
—System
(S1)+2
Modification
specification
Specify the modification.
0001
H
: Station No. setting
0001
H
User
(S1)+3 Own station No. Specify a station No. of the own station. 1 to 120 User
(S1)+4 to
(S1)+9
— Unused 0 User
255 2
Station No.
(SW0042)
UINI
CC-Link IE Controller
Network module
CPU module
(S1)
[Own station]