489
CHAPTER 9 DEDICATED INSTRUCTIONS
9
9.20 J(P)/G(P).RIWT (Data Write to Programmable Controllers on Target Station)
9.20 J(P)/G(P).RIWT (Data Write to Programmable Controllers
on Target Station)
This instruction writes the specified points of data to the target station's device.
(1) Setting data
*1 Local devices and file registers for each program cannot be used as devices used in setting data.
Setting
data
Available devices
Internal device
(System, User)
File
register
R, ZR
Link direct
device J\
Intelligent
function
module device
U\G
Index
register Zn
Constant
Others
Bit Word Bit Word K,H $
(S1) — —
(S2) — —
(D) —
Setting data
*1
Description Data type
Jn
Network number of the own station (1 to 239, 254)
254: The network specified in Valid module during other station access
Binary 16 bits
Un
Start I/O number of the own station's CC-Link IE Controller Network module
(00 to FE
H
: The higher two digits of the 3-digit I/O number)
(S1)
Start device of the own station that stores control data.
( Page 490, Section 9.20 (2))
Device name
(S2) The own station's start device where write data are stored.
(D)
The own station's device that is turned on for one scan upon completion of the
instruction.
(D) + 1 also turns on if the instruction execution has failed.
Bit
J.RIWT
JP.RIWT
J.RIWT
JP.RIWT
G.RIWT
GP.RIWT
G.RIWT
GP.RIWT
Start contact
[Instruction format][Execution
condition]
[Instruction
symbol]
Start contact
Jn (S1) (S2) (D)
Jn (S1) (S2) (D)
Un (S1) (S2) (D)
Un (S1) (S2) (D)
Start contact
Start contact