490
(2) Control data
(a) Control data
*1 The setting side is as shown below.
User: Before execution of the dedicated instruction, data must be set by the user.
System: The CPU module stores the execution result of the dedicated instruction.
Device Item Setting data Setting range
Setting
side
*1
(S)+0 Completion status
The instruction completion status is stored.
0: Normal
Other than 0: Error ( Page 511, Section 10.2)
When the target station is other than the CC-Link IE Controller
Network module, refer to the manual for the target station for error
codes.
— System
(S)+1 Target station No. Specify the station No. of the target station. 1 to 120 User
(S)+2
Access code/
Attribute code
Specify the access and attribute codes of the write target device.
Refer to (b) User
(S)+3 Device No. Specify the start No. of the device to which data are written. Within device range User
(S)+4
Number of points
to write
Specify the size of the data to be written in units of words. 1 to 480 User
Access code
b15 to b8 b7 to b0
Attribute code