D LINK LED is flashing.
Check error factors with the CC IE Control
diagnostics and take corrective actions according
to the troubleshooting section.
Start the PLC diagnostics in the programming tool.
Perform a unit test to the CC-Link IE controller
network module.
After completion of the test, set the control station
to online.
Restart cyclic transmission.
QCPU User's Manual
(Hardware Design, Maintenance and Inspection)
Check the error details and take corrective actions.
Is D LINK LED turned ON?
Has a link stop been executed?
Has a circuit test been executed?
Not occurred
ON
No
Not executed
Not executed
Has a stop error other than the
above occurred in the CPU module?
Has a LINK PARA.ERROR or
NETWORK PARAMETER ERROR
occurred in the CPU module?
Yes
No
Occurred
Check the network parameters.
If the error has occurred in a Basic model QCPU
or safety CPU, check its LB/LW send range in
"Network range assignment" of the control station.
Yes
Turn ON the power supply module.
Is the power supply module ON
for the CC-Link IE controller network module with
external power supply function?
OFF
Executed
Executed
End